Overview:
The isolating switch is of a unipolar type, and the three poles can be connected by a connecting rod into a three-pole type that can be linked. It is equipped with CS11 or CS8-6D manual mechanism. CS17 is used for the isolating switch with double grounding device. (The electric mechanism can be equipped as needed).
The isolation switch has reasonable structure and flexible operation: it can be used for single pole or three poles, and the installation is convenient: the touch knife is opened, and the insulation is safe and reliable. It can also be grounded or double grounded according to user needs.
Name | Unit | GW4-12 | GW4-40.5 | GW4-72.5 | GW4-126 | GW4-160G | GW4-145 | |
Rated Voltage | KV | 12 | 40.5 | 72.5 | 126 | 126 | 145 | |
Rated current | A |
200 400 630 1000 1250 |
630 1000 2000 2500 |
630 1250 2000 2500 |
630 1250 2000 2500 |
630 1250 |
630 1250 2000 2500 |
|
Rated short-circuit withstand current (RMS) | KA |
16 20 25 |
20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 40(46) |
20 31.5 |
20 31.5 40(46) |
|
Rated peak withstand current (RMS) | KA |
40 50 63 |
50 80 100(104) |
50 80 100(104) |
50 80 100(104) |
50 80 |
50 80 100(104) |
|
1min power frequency withstand voltage (peak) | To the ground | KV | 42 | 80 | 140 |
185 (230) |
185 | 275 |
Fracture | 48 | 90 | 160 |
210 (265) |
210 | 315 | ||
Lightning impulse withstand voltage (peak) | To the ground | 75 | 185 | 325 |
450 (550) |
450 | 650 | |
Fracture | 85 | 215 | 375 |
520 (530) |
550 | 750 | ||
Terminal horizontal tension | N | 250 |
490 (735) |
735 | 735 | 735 | 980 | |
Monopolar weight | KG | 60 | 80 | 200 | 240 | 240 | 300 | |
Remarks | Suitable for altitude 2000m | Suitable for 110kv altitude 4000m |