12kv Outdoor High Voltage Isolating Switch Disconnecting AC Switch

Type:
High-voltage
Origin:
Zhejiang, China

Overview:

The isolating switch is of a unipolar type, and the three poles can be connected by a connecting rod into a three-pole type that can be linked. It is equipped with CS11 or CS8-6D manual mechanism. CS17 is used for the isolating switch with double grounding device. (The electric mechanism can be equipped as needed).

The isolation switch has reasonable structure and flexible operation: it can be used for single pole or three poles, and the installation is convenient: the touch knife is opened, and the insulation is safe and reliable. It can also be grounded or double grounded according to user needs.

Name Unit GW4-12 GW4-40.5 GW4-72.5 GW4-126 GW4-160G GW4-145
Rated Voltage KV 12 40.5 72.5 126 126 145
Rated current A 200
400
630
1000
1250
630
1000
2000
2500
630
1250
2000
2500
630
1250
2000
2500
630
1250
630
1250
2000
2500
Rated short-circuit withstand current (RMS) KA 16
20
25
20
31.5
40(46)
20
31.5
40(46)
20
31.5
40(46)
20
31.5
20
31.5
40(46)
Rated peak withstand current (RMS) KA 40
50
63
50
80
100(104)
50
80
100(104)
50
80
100(104)
50
80
50
80
100(104)
1min power frequency withstand voltage (peak) To the ground KV 42 80 140 185
(230)
185 275
Fracture 48 90 160 210
(265)
210 315
Lightning impulse withstand voltage (peak) To the ground 75 185 325 450
(550)
450 650
Fracture 85 215 375 520
(530)
550 750
Terminal horizontal tension N 250 490
(735)
735 735 735 980
Monopolar weight KG 60 80 200 240 240 300
Remarks           Suitable for altitude 2000m Suitable for 110kv altitude 4000m